概要:摘要:针对某原油处理厂建筑物内DCS(集散控制系统)模块及厂区传感器遭雷击损坏情况,进行了电子设备雷电电磁脉冲防护原理分析,制定出DCS系统雷电电磁脉冲防护设计方案。 Abstract Based on DCS module and transducer stroken by lightning in buildings of crude oil plant, the paper analyses protection principle of electro-magnetism pulse on electronic equipments. It put forward a protection scheme for lightning electro-magnetism pulse on DCS system.Key words DES system Transducer LEMP Shielding Equipotential bonding Earthing1 引言某座濒临渤海的陆上终端原油处理厂,配有先进的DCS集散

建筑物内DCS系统防雷电电磁脉冲设计,标签:建筑设计,建筑设计规范,http://www.65jz.com

摘要:针对某原油处理厂建筑物内DCS(集散控制系统)

模块及厂区传感器遭雷击损坏情况,进行了电子设备

雷电电磁脉冲防护原理分析,制定出DCS系统雷电电磁脉

冲防护设计方案。

Abstract Based on DCS module and transducer

stroken by lightning in buildings of crude

oil plant, the paper analyses protection

principle of electro-magnetism pulse on

electronic equipments. It put forward a

protection scheme for lightning electro-magnetism

pulse on DCS system.
Key words DES system Transducer LEMP

Shielding Equipotential
bonding Earthing

1 引言
某座濒临渤海的陆上终端原油处理厂,配有先进的DCS集散控制系统。

2000年雨季6个大罐及污水区PTl00温度传感器、燃料油加热器温度变

送器、汽水换热器压力变送器、净水池液位变送器及相对应的中控室

A1630、A1635模块两次遭雷击损坏。根据现场电子设备遭雷击损坏情况

的原因分析,制定出DCS系统防雷改造设计方案,并已实施。
2 DCS系统模块及传感器损坏原因分析
2.1 厂区环境及防雷接地现状
该厂距渤海40m,征地980亩,两面邻海,四周空旷。进出中心

控制室DCS系统模块的控制电缆在厂区电缆桥架内敷设,桥架高5m,

该地区年平均雷暴日数为30天。
厂区内壁厚大于4mm储油罐采取了防直击雷措施,对金属油、